The clamp with earth cable is used to make the electrical connection between the power source and the base material to be welded. The section and length of the cable are determined by the maximum current from the power source.
What does Grounding have to do with Arc Welding Safety Earth Clamp,Copper Earth Clamp,Copper Grounding Clamp,Brass Clamp For Earth Changzhou Edaweld Trading Company Limited , https://www.edaweld.com
Most friendly operation interface Model No.: AT300B
----------------------Walk-through Metal Detector
--------------------------------------------------------------------------------------------------------------------------
Perfect weather-proofing design for outdoor use
Easy to Install, Simple to Operate
Technical specification
Â
Electrical current:Â
AC100V~240VÂ Â Â Â 50/60HzÂ
Power:Â
10W
Work environment:
-20ºC ~ +45ºC Â
Gross Weight:
70kg
Outer frame:
2220mm (h) x 820mm (w) X 610mm (d)
Inner frame:Â
2000mm (h) X 700mm (w) X 610mm (d)Â
Characteristic
Â
IP55 weather proof design, supporting outdoor work Operation way: remote control only Two LED light bars on both door panels: gives alarm corresponding to the height or human body. 6/12/18 Pinpoint zones to precisely identify multiple target locations from head to toe. Advanced broadband detection technology: can detect ferrous and non-ferrous articles. Sensitivity adjustable from Level 0 to 299 High: Can detect a clip Low: Detect big metal articles such as: knife, gun, and copper, aluminums, zinc (more than 150g), ignoring metal in belt button, shoes. Shock proof to avoid false alarm Sound and light alarm Intelligent traffic and alarm counters that calculate traffic flow and resultant alarms. Tamper-Proof: operate program is protected by password. Adjustable operating frequencies---eliminate the potential effects from X-ray units, radios and other electrical interference sources. Mix distance between two Walk-thru: 0.3 meters at low sensitivity, 0.5 meters at high sensitivityÂ
Harmless to pregnant woman and heart pacemakerÂ
Â
(Optional)Connect with computer, camera, turnstile, etc
Â
Â
Â
Â
Â
--------------------------------------------------------------------------------------------------------------------------
Features of super metal scanner door:
1. Materials and displaying: Adoption of Fire board materials, the ultra-large LED displaying panel, convenient for the work of the operator.
2. Six detecting areas: Allocation of six mutual over-lapping detecting areas, Simultaneous alarming from multi-areas and accurately ascertaining the location Of the metal articles according to the layout of the metal articles.
3. Operation with both English and Chinese languages: LCD can be operated with menus In both English and Chinese, easy and convenient.
4. Adjustable area sensibility: With the highest sensibility, it can detect the metal Article as small as the clip. With the range of 0-100, it can be adjusted the Sensibility easily, pre-set the weight, volume, size and location in respect of the metal Articles and eliminate the false alarming for the coin, key, jewelry, leather belt button, etc.
5. High capability of anti-interference: The adoption of digital, analogy and left and right Balanced technology can prevent false or omitted alarming, which greatly enhance The capability of anti-interference.
6. Protection with password: The protection from the password can only allow the Authorized person for the operations. It is highly safe.
7. Functions of statistic counting: The intelligent counter can calculate the number of the Passenger flow and the times of alarming.
8. Harmless to human body: The product is harmless to heart pacemaker installed in Human body, pregnant women, magnetic floppy, recording tapes, etc.
9. Convenience in installation: EAST series products adopt integration design. It only Takes twenty minutes to install the gate or take it apart.
Most friendly operation interface Model No.: AT300B
----------------------Walk-through Metal Detector
--------------------------------------------------------------------------------------------------------------------------
Perfect weather-proofing design for outdoor use
Easy to Install, Simple to Operate
Technical specification
Â
Electrical current:Â
AC100V~240VÂ Â Â Â 50/60HzÂ
Power:Â
10W
Work environment:
-20ºC ~ +45ºC Â
Gross Weight:
70kg
Outer frame:
2220mm (h) x 820mm (w) X 610mm (d)
Inner frame:Â
2000mm (h) X 700mm (w) X 610mm (d)Â
Characteristic
Â
IP55 weather proof design, supporting outdoor work Operation way: remote control only Two LED light bars on both door panels: gives alarm corresponding to the height or human body. 6/12/18 Pinpoint zones to precisely identify multiple target locations from head to toe. Advanced broadband detection technology: can detect ferrous and non-ferrous articles. Sensitivity adjustable from Level 0 to 299 High: Can detect a clip Low: Detect big metal articles such as: knife, gun, and copper, aluminums, zinc (more than 150g), ignoring metal in belt button, shoes. Shock proof to avoid false alarm Sound and light alarm Intelligent traffic and alarm counters that calculate traffic flow and resultant alarms. Tamper-Proof: operate program is protected by password. Adjustable operating frequencies---eliminate the potential effects from X-ray units, radios and other electrical interference sources. Mix distance between two Walk-thru: 0.3 meters at low sensitivity, 0.5 meters at high sensitivityÂ
Harmless to pregnant woman and heart pacemakerÂ
Â
(Optional)Connect with computer, camera, turnstile, etc
Â
Â
Â
Â
Â
--------------------------------------------------------------------------------------------------------------------------
Features of super metal scanner door:
1. Materials and displaying: Adoption of Fire board materials, the ultra-large LED displaying panel, convenient for the work of the operator.
2. Six detecting areas: Allocation of six mutual over-lapping detecting areas, Simultaneous alarming from multi-areas and accurately ascertaining the location Of the metal articles according to the layout of the metal articles.
3. Operation with both English and Chinese languages: LCD can be operated with menus In both English and Chinese, easy and convenient.
4. Adjustable area sensibility: With the highest sensibility, it can detect the metal Article as small as the clip. With the range of 0-100, it can be adjusted the Sensibility easily, pre-set the weight, volume, size and location in respect of the metal Articles and eliminate the false alarming for the coin, key, jewelry, leather belt button, etc.
5. High capability of anti-interference: The adoption of digital, analogy and left and right Balanced technology can prevent false or omitted alarming, which greatly enhance The capability of anti-interference.
6. Protection with password: The protection from the password can only allow the Authorized person for the operations. It is highly safe.
7. Functions of statistic counting: The intelligent counter can calculate the number of the Passenger flow and the times of alarming.
8. Harmless to human body: The product is harmless to heart pacemaker installed in Human body, pregnant women, magnetic floppy, recording tapes, etc.
9. Convenience in installation: EAST series products adopt integration design. It only Takes twenty minutes to install the gate or take it apart.
?
Grounding of electrical circuits is a safety practice that is documented in various codes and standards. A typical arc welding setup may consist of several electrical circuits. Applying and maintaining proper grounding methods within the welding area is important to promote electrical safety in the workplace. Associated processes such as plasma cutting will also benefit from proper grounding. The important grounding topics in a typical welding environment are discussed.
Grounding and Arc Welding Safety
Welding Machine Ground
Welding Machines that utilize a flexible cord and plug arrangement or those that are permanently wired into an electrical supply system contain a grounding conductor. The grounding conductor connects the metal enclosure of the welding machine to ground. If we could trace the grounding wire back through the electrical power distribution system we would find that it is connected to earth, and usually through a metal rod driven into the earth.
Grounding and Arc Welding Safety
The purpose of connecting the equipment enclosure to ground is to ensure that the metal enclosure of the welding machine and ground is at the same potential. When they are at the same potential, a person will not experience an electrical shock when touching the two points. Grounding the enclosure also limits the voltage on the enclosure in the event that insulation should fail within the equipment.
The current carrying capability of the grounding conductor is coordinated with the overcurrent device of the electrical supply system. The coordination of ampacity allows the grounding conductor to remain intact even if there is an electrical fault within the welding machine.
Some welding machines may have a double insulated design. In this case, a grounding conductor connection is not required. This type of welding machine relies on extra insulation to protect the user from shock. When double insulation is present it is identified by a "box within a box" symbol on the rating plate.
Grounding and Arc Welding Safety
For small welding machines that utilize a plug on the end of a power cord, the grounding conductor connection is made automatically when the welding machine is plugged into the receptacle. The grounding pin of the plug makes a connection within the receptacle. The use of adapters that effectively remove the grounding pin connection at the plug is not recommended. Furthermore, do not cut off or remove the grounding pin from the plug. All safety benefit of the grounding conductor is lost without the connection.
Grounding and Arc Welding Safety
Receptacle circuit testers will easily check the continuity of the grounding conductor. Receptacle circuit testers for 120-volt circuits are available at electrical supply or hardware stores; these inexpensive test devices plug into an electrical outlet. Indicator lights show whether the grounding circuit is available at the outlet, as well as other circuit tests. If the test device shows the absence of a ground connection or other circuit problem, call a qualified electrician for assistance. This is a simple test and should be done periodically. Consult with a qualified electrician to test circuits greater than 120 volts.
Grounding and Arc Welding Safety
Workpiece Ground
The welding circuit consists of all conductive material through which the welding current is intended to flow. Welding current flows through the welding machine terminals, welding cables, workpiece connection, gun, torch, Electrode Holder and workpiece. The welding circuit is not connected to ground within the welding machine, but is isolated from ground. How do we ground the welding circuit?
According to ANSI Z49.1, "Safety in Welding, Cutting and Allied Processes," the workpiece or the metal table that the workpiece rests upon must be grounded. We must connect the workpiece or work table to a suitable ground, such as a metal building frame. The ground connection should be independent or separate from the welding circuit connection.
Grounding and Arc Welding Safety
Grounding the workpiece has similar benefit to grounding the welding machine enclosure. When the workpiece is grounded, it is at the same potential as other grounded objects in the area. In the event of insulation failure in the arc welding machine or other equipment, the voltage between the workpiece and ground will be limited. Note that it is possible to have an ungrounded workpiece, but this requires the approval of a qualified person.
The Workpiece Connection is not a Ground Clamp
"Ground clamp" and "ground lead" are common terms used by many welders. The workpiece is connected to a welding cable typically by means of a spring loaded clamp or screw clamp. Unfortunately, a workpiece connection is often incorrectly called a "ground clamp" by many welders and the workpiece lead is incorrectly called "ground lead." The welding cable does not bring a ground connection to the workpiece. The ground connection is separate from the workpiece connection.
High Frequency Ground
Some welding machines utilize starting and stabilizing circuits that contain a high frequency voltage. This is common on Tungsten Inert Gas (TIG) welding machines. The high frequency voltage may have frequency components that extend into the megahertz region. In contrast, the welding voltage may be as low as 60 Hertz.
High frequency signals have a tendency to radiate away from the welding area. These signals may cause interference with nearby radio and television reception or other electrical equipment. One method to minimize the radiation of high frequency signals is to ground the welding circuit. The welding machine instruction manual will have specific instructions on how to ground the welding circuit and components in the surrounding area to minimize the radiation effect.
Portable and Vehicle Mounted Welding Generator Grounding
Portable and vehicle mounted arc welding generators often have the capability to supply 120 and 240 volt auxiliary power. These generators are used in remote locations away from an electrical power distribution system. A convenient earth ground is not usually available for connection. Should the generator frame be grounded?
The rules for grounding depend on the specific use and design of the auxiliary power generator. Most applications fall into one of the two categories summarized below:
1. If all of these requirements are met, then it is not required to ground the generator frame:
The generator is mounted to truck or trailer
The auxiliary power is taken from receptacles on the generator using a cord and plug arrangement
The receptacles have a grounding pin
The frame of the generator is bonded, or electrically connected, to the truck or trailer frame
2. If either of these conditions are met, then the generator frame must be grounded:
The generator is connected to a premises wiring system. For example, to supply power to a house during a blackout.
The auxiliary power is hard wired into the generator without the use of cords and plugs.
The summary above does not go into details and the reader is urged to consult their local electrical codes and ANSI/NFPA 70, "National Electrical Code" for the specifics.
Extension Cord Grounds
Extension cords should be periodically tested for ground continuity. Extension cords lead a rough life while lying on the ground; they are under foot and prone to damage. The use of a receptacle circuit tester will confirm that all of the connections are intact within the cord, plug and receptacle.
Welding Circuit Shock Hazards
Utilizing proper grounding in the welding environment is a good practice, but it does not remove all possibility of electrical shock. The welding circuit is energized by welding voltage. A person will receive a shock if they become the electrical path across the welding circuit. Precautions must be taken to insulate the welder from the welding circuit. Use dry insulating gloves and other insulating means. Also maintain insulation on weld cables, electrode holders, guns and torches to provide protection.
Similarly, electric shock originating from the electrical supply system can be prevented. Proper maintenance of electrical equipment and extension cords will insulate the welder from electrical sources.
Information Sources
American Welding Society, ANSI Z49.1:2005 "Safety in Welding, Cutting, and Allied Processes."

National Fire Protection Association, NFPA 70, "National Electrical Code", 2005.

American Welding Society, Safety and Health Fact Sheet No. 29, "Grounding of Portable and Vehicle Mounted Welding Generators", July 2004.

American Welding Society, AWS A3.0-2001, "Standard Welding Terms and Definitions."
Model NO.: AT300B
Trademark: Safeway System
Transport Package: Wooden
Specification: CE, ROHS, SGS
Origin: China
HS Code: 8543709100
Model NO.: AT300B
Trademark: Safeway System
Transport Package: Wooden
Specification: CE, ROHS, SGS
Origin: China
HS Code: 8543709100